Commissioning security module (firewall) FN2009
-
A1
Creating IP service definitions
23
100 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
Loading the network settings to FN2009-A1
ϖ MAC address is entered.
ϖ IP addresses are entered.
1. Highlight the FN2009-A1 module in the project.
2. Select the 'Transfer > 'To Module' menu.
The network settings are loaded to FN2009-A1.
Network settings are entered.
23.4 Creating IP service definitions
NOTICE
Different
BACnet port settings in FN2009
-
A1 and
SintesoWorks
No communication possible
Configure the same BACnet port in FN2009
-
A1 and
SintesoWorks
.
1. Open the 'Options' > 'IP Service Definitions' menu.
The 'IP Service Definitions' window is opened.
2. Select the 'IP Services' tab.
3. Click on 'Add IP Service'.
One row can be edited for one IP service.
4. Enter the two IP services required as shown in the figure above:
'Name': Tool, 'Protocol': udp, 'Source Port': *, 'Target Port': 51000
'Name': BACnet, 'Protocol': udp, 'Source Port': *, 'Target Port': 47808
Required IP services are created.
5. Select the 'ICMP' tab.
6. Click on 'Add ICMP Service'.
One row can be edited for one ICMP service.