Updating the firmware
Station: Updating the FW of the main CPU and additional CPUs
29
122 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
29.2.5 FW update for main CPU and additional CPUs
The procedure for updating the main CPU and additional CPUs depends on
whether the PMI & mainboard FCM2004, FCM2027 or the CPU card FCC2004 is
used in the 'Station'. The procedures are described in the following chapters:
'PMI & mainboard FCM2004 [ 122]'
'PMI & mainboard FCM2027 [ 125]'
'CPU card FCC2004 [ 127]'
29.2.5.1 PMI & mainboard FCM2004
ϖ You are familiar with the information in chapter 'Preparation and security
[➙ 117]'.
1. Select 'Update' > 'FW update main and additional CPUs' from the menu bar.
2. If the 'Password check' window is open, enter the password '1234' and click on
'OK'.
3. NOTICE! Data loss. Save the configuration data before updating the firmware.
Saving the configuration data also backs up specific system data which is
only available on the 'Station'. This includes modified customer texts, time
stamps of recent alarms, or persistent commands.
The 'FW update main and additional CPUs' window opens.
4. Select the desired firmware version.
5. The firmware update can be started in two ways:
Start the firmware update in SintesoWorks.
or
Start the firmware update at the 'Station'. The procedure is described in
the following section.
Initializing the '
Station
' instead of installing the
BDV saves time. During
initialization, the BDV and the configuration data are loaded to the 'Station'.
You will find information on
troubleshooting for the firmware update in chapter
'Error during firmware update [ 132]'.