Updating the firmware
Station: Updating the FW of the main CPU and addit
ional CPUs
29
125 |
188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
29.2.5.2 PMI & mainboard FCM2027
ϖ You are familiar with the information in chapter 'Preparation and security
[➙ 117]'.
1. Select 'Update' > 'FW update main and additional CPUs' from the menu bar.
2. If the 'Password check' window is open, enter the password '1234' and click on
'OK'.
3. NOTICE! Data loss. Save the configuration data before updating the firmware.
Saving the configuration data also backs up specific system data which is
only available on the 'Station'. This includes modified customer texts, time
stamps of recent alarms, or persistent commands.
The 'FW update main and additional CPUs' window opens.
4. Select the desired firmware version.
5. The firmware update can be started in two ways:
Start the firmware update in SintesoWorks.
or
Start the firmware update at the 'Station'. The procedure is described in
the following section.
Initializing the '
Station
' instead of installing the
BDV saves time. During
initialization, the BDV and the configuration data are loaded to the 'Station'.
You will find
information on troubleshooting for the firmware update in chapter
'Error during firmware update [ 132]'.

Table of Contents