Updating the firmware
Station: Updating the FW of the main CPU and additional CPUs
29
126 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
Starting the firmware update at the 'Station' – FCM2027
1. Select 'Initiate update at station'.
The following window is opened:
2. Keep the 'S32' button on the rear of the operating unit pressed and press
<Acknowledge> on the Person Machine Interface at the same time for
approx. 5 s until the 'Station' restarts.
A peeping sound confirms the function is being executed.
The firmware is updated and the 'Station' restarts several times. This
procedure takes up to ten minutes.