Changing and expanding the FDnet/C
-
NET detector line
Permanently removing stationary devices
14
51 |
188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
14.3 Permanently removing stationary devices
You will find additional information about the individual steps on the sp
ecified
pages.
1. Switch the FDnet detector line off. Link [ 82]
2. Remove the FDnet devices. Link [ 85]
3. Connect the PC to the 'Station'. Link [ 27]
4. Load the configuration from the 'Station' to the PC. Link [ 32]
5. Remove the physical representation of the devices and the logical elements in
SintesoWorks. Link [ 86]
6. Switch the FDnet detector line on. Link [ 83]
7. Load the configuration from the PC to the 'Station'. Link [ 30]
8. Disconnect the PC from the 'Station'. Link [ 27]
You can also delete the physical representation of the
FDnet
devices individually
via the control panel's Person Machine Interface. Link [ 86]
14.4 Removing or replacing non-stationary devices
14.4.1 Temporarily removing an individual non-stationary device
It may be possible that an FDnet device must be temporarily removed from the
base. Afterwards the same FDnet device must be re-inserted at exactly the same
place in the FDnet.
Document the serial number or address and the position in the
FDnet
for each
device in order to enable the device to be placed in the same position following its
removal.
1. Remove the FDnet device.
The control panel detects that the FDnet device is missing and reports a
'Fault'.
2. Perform the necessary activities.
3. Re-insert the FDnet device in the FDnet in the same, previous position.
4. Acknowledge the 'Fault'.
If this 'Fault' is no longer displayed, the control panel updates the settings of
the re-inserted FDnet device.
If this 'Fault' is still displayed, and / or the detector line is not in normal
operation, the detector line has to be restarted.
The work described in this chapter may be performed when the
FDnet
detector
line is switched on.
See also
1 Restarting the detector line [ 83]