standalone 'Station' without PC
Configuring the power supply
6
39 |
Building Technologies
6.1 Configuring the power supply
If the ↑ 'Station' is equipped with a power supply and batteries, the power supply
does not have to be configured. In all other cases the power supply must be
configured. This may be done by wiring accordingly.
The following table shows the cases in which the monitoring signals of the power
supply must be re-wired.
Operation mode
Connector on
periphery board
Connect with
Operation without
batteries
X1 / pin 1 '#BATT' X1 / pin 4 #COMMON
Operation without
power supply unit
X1 / pin 1 '#BATT' X1 / pin 4 #COMMON
X1 / pin 2 '#CONV' X1 / pin 4 #COMMON
X1 / pin 3 '#MAINS' X1 / pin 4 #COMMON
Table 2: Configuring the power supply
You will find the pin assignments in document 008837. See chapter 'Applicable
documents'.
See also
1 Applicable documents [➙ 11]
6.2 Entering customer texts using the Person Machine
Interface
1. Select 'Topology' > ↑ 'Detection tree' > 'Area' > 'Section' > 'Zone' in the main
menu.
2. Select the element you want to label with a customer text.
3. Press the 'More Options' softkey and select 'Execute commands'.
4. Select the 'Set customer text' command.
5. Enter the customer text using the numeric keypad.
6. Press <ok> to save the customer text. There is no need to restart the ↑ Station.
Showing the customer text on the display
● All elements apart from 'Zone':
If a message associated with an element appears, the corresponding customer
text is displayed. If no customer text is assigned to this element, the customer
text of the next superordinate element, e.g. 'Detector' > 'Line' > 'Line card',
appears.
● 'Zone' element:
If an alarm message for a 'Zone' appears, the customer text of the detector
(sensor) is displayed. The customer text of the 'Detector' appears if no
customer text is assigned to the 'Zone'. The customer text of the next
superordinate element ('Zone' > 'Detector' > 'Zone' > 'Section') appears if no
customer text is assigned to the 'Area' either.