30.4 Preparatory work
Inform the system owner
Inform the system owner of the scope and expected duration of work and also that
↑ 'Site' operation will be restricted.
For large-scale systems fill out the system shutdown notification sheet and have
this signed by the system owner.
Block system components
Block the following system components:
● Remote alarm (log out on the receiving center)
● 'Fire controls' and alarm equipment
● Extinguishing stations
Specify the procedure
Stipulate the times for the following test sequences with the system owner:
● Test alarms (including remote transmission)
● Performance check for 'Fire controls'
● Additional instructions (if required)
● Clarifications (if required)
30.5 Test system data
System test manual
Ensure that the system test manual is available and up to date.
Remote transmission
Check that the phone numbers and the names of the remote transmission
receivers are up to date.
Data backup for ↑ 'Site'
1. Check that the system data are saved.
Two copies must be archived with the 'Site', one copy with the technical
department.
2. Update the system data when the configuration is changed.
3. Note the date of execution in the system test manual.
Firmware
1. Read out the current firmware version from the ↑ 'Station': To do this, select
'Topology' > 'Hardware tree' > 'Station' > 'MoreOptions' > 'Show details' in the
main menu.
2. Do not replace the current firmware version with the latest version unless this is
necessary to correct faults or add functions.
'Event memory'
Check the content of the 'Event memory' and take the necessary measures, e.g.,
switch on elements that have been switched off temporarily.