Commissioning of control panel
with interactive detector line
Commissioning of interactive detector line for AlgoRex data migration
19
70 | 188
19.1 Commissioning of interactive detector line for
AlgoRex data migration
Creating the ↑ pre-configuration for AlgoRex data migration
If you are using the ↑ line card (interactive) for AlgoRex data migration, you must
create a pre-configuration. To do this, migrate the AlgoRex configuration data for
the FS20 fire detection system. You will find more information about AlgoRex data
migration in document 009078. See chapter 'Applicable documents'.
Prerequisites
● The ↑ 'Station' is installed, but the batteries are not connected yet.
● The cables for the ↑ detector lines and the mains supply have been inserted in
the 'Station', but not yet connected.
● SintesoWorks is installed on the PC.
● The latest firmware is installed on the 'Station'.
● The latest ↑ BDV is installed on the 'Station' or is available on the PC.
You will find additional information about the individual steps on the specified
pages.
1. Create the ↑ pre-configuration of the interactive detector line. You will find
information about AlgoRex data migration in document 009078. See chapter
'Applicable documents'.
2. Load the pre-configuration in 'SintesoWorks'.
3. Prepare the ↑ 'Station' for commissioning – without ↑ BDV installation.
Link [➙ 77]
4. Connect the PC to the 'Station'. Link [➙ 27]
5. Load the configuration from the PC to the 'Station'. Link [➙ 30]
6. Test the function of the 'Site'. Link [➙ 91]
7. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [➙ 30]
8. Disconnect the PC from the 'Station'. Link [➙ 27]
9. Perform the completion tasks. Link [➙ 91]