Updating the firmware
Station: Updating the FW of the a
dditional CPUs only
29
134 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
29.3.3 FW update for additional CPUs
NOTICE
Updating the firmware of the degraded mode
module FN2001
If the firmware of the degraded mode module FN2001 has to be updated, it must
be temporarily connected to the slot for the main module FN2001 (from slot X12
to X13).
ϖ Familiarize yourself with the information in the chapter 'Preparation and
security'.
1. Select 'Update' > 'FW update additional CPUs' from the menu bar.
2. If the 'Password check' window is open, enter the password '1234' and click on
'OK'.
The 'Connect' window opens.
3. Select the connection type:
Select 'Local connection' to establish a connection to the connected
standalone or SAFEDLINK 'Station'.
Select 'Connection to GAP' to establish a connection via GAP to a
networked 'Station'. Enter the address of the 'Station' you want to update in
the 'Target station address' field. If you want to update the GAP 'Station'
itself, enter '0'.
4. Click on 'OK'.
The 'FW update additional CPUs' window opens.
The checkboxes for the CPUs that can be updated are checked in column
'Update'.
5. Select the CPUs you want to update and click on 'Start'.
The 'Set access level' window opens.
6. Press <MENU> on the 'Station' and enter a valid PIN.
7. Click on 'OK' in the 'Set access level' window.
The CPUs are updated.
The 'Information' window is opened after updating.
8. Note the update information and information about other procedures in the
'Information' window.
9. Click on 'OK'.
The 'Station' is restarted.
After a few minutes, the 'Buzzer' sounds twice.