Loading...
Changing and expanding the FDnet/C
-
NET detector line
Removing or replacing non
-
stationary devices
14
52 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
14.4.2 Temporarily removing multiple non-stationary devices
For the purpose of painting work, it may be necessary to temporarily remove the
FDnet devices in a room. Each FDnet device must then be re-inserted in its original
base. The FDnet devices may not be exchanged.
You will find additional information about the
individual steps on the specified
pages.
Mark the allocation of the devices to the respective base to avoid additional work
steps.
1. Switch the 'Zone' off. Link [ 82]
2. Remove the FDnet devices from the base and insert the dummy detector if
necessary.
3. Perform the tasks.
4. Re-insert the FDnet devices to the respective position.
5. Switch the 'Zone' on. Link [ 83]
For all the re-inserted FDnet devices, a localization fault is displayed.
6. Restart the FDnet detector line. Link [ 83]
If detectors have been swapped over or are missing, the following messages are
shown on the display of the Person Machine Interface:
'Zone', 'Serial no. ("ID-Nr.")', 'Dev.location fault'
The work described in this chapter may be performed when the
FDnet
detector
line is switched on.
14.4.3 Permanently removing non-stationary devices
You will find additional information
about the individual steps on the specified
pages.
1. Switch the FDnet detector line off. Link [ 82]
2. Remove the FDnet devices and their bases. Link [ 85]
3. Switch the FDnet detector line on. Link [ 83]
4. Delete the FDnet devices individually via the Person Machine Interface on the
control panel. Link [ 86]
5. Connect the PC to the 'Station'. Link [ 27]
6. Load the configuration from the 'Station' to the PC. Link [ 32]
7. Remove the logical elements in SintesoWorks. Link [ 86]
8. Load the configuration from the PC to the 'Station'. Link [ 30]
9. Disconnect the PC from the 'Station'. Link [ 27]

Table of Contents