Connectivity and communication with 'Station'
Connecting the PC to the station
4
27 |
188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
4.3 Connecting the PC to the station
For most commissioning, maintenance and repair work a PC with installed
SintesoWorks is required. The figure below shows the connection between the PC
and 'Station'.
Figure 1: Rear panel of operating unit and PC
LAN Ethernet connection
1 Cable, type CAT 5 or CAT 7, crossover, max. 100 m
4.4 Disconnecting the PC from the station
As the IP address is bound to the MAC address while there is a connection
between the PC and the 'Station' and as it remains in the cache even in the case
of a short break in the connection of 2 min., you must observe the following
instructions.
NOTICE
Incorrect disconnection of '
Station
'
Establishing a connection to other 'Station' is not possible
Disconnect the PC from the '
Station
' as described in the following instructions.
The connection between the PC and the 'Station' must be disconnected as follows:
1. Select 'SintesoWorks' > 'Commissioning' in Disconnect.
2. Disconnect the cable connection between PC and 'Station'.
3. Wait 2 min. before you establish a connection to another 'Station'.
LAN
1
1