Updating the firmware
Updating the FW of the peripheral devices
29
147 |
188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
29.8.5 Radio gateway FDCW221
WARNING
Incorrect assignment between
detector/detector zone and customer text
Misleading messages in the event of an alarm
Never change the wiring during the firmware update.
The firmware must be updated individually for each radio gateway
FDCW221.
Following a FW update, the FDCW221 has to detect all the devices again
before you can switch the 'Line' back on.
NOTICE
'
Line
' switched back on too soon
'Device location fault' is displayed
At the end of the FW update, wait until the FDCW221 has detected all the
devices again.
The 'Line' may only be switched back on once the FDCW221 has detected all
the devices again.
Preparation
ϖ The FDCW221 is internally fed by a 9 V battery.
ϖ The driver for the MCL-USB adapter is installed on the PC.
1. Select the 'File' > 'Import new resource package' menu item.
2. In the selection window, open an F-FXS2001-XX_x_x_...zip file matching the
Site.
3. Open the FDCW221 and connect the PC via the MCL-USB adapter FDUZ221
or FDUZ227 to the device.
Figure 11: Connection of the PC to the FDCW221
FDUZ221 /
FDUZ227
MCL-USB adapter (interface USB/MC-LINK)
FDCW221 Radio gateway
MC-Link
FDCW221
FDUZ221/FDUZ227
USB