Changing and expanding the FDnet/C
-
NET detector line
Replacing 'Manual call point' of the same type
14
54 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
14.4.5.1 Replacing a device in the 'Zone'
1. Select the 'Zone' in which you have replaced a device in SintesoWorks. The
'Find' or 'Find and replace' functions can be used to do this.
2. Replace the FDnet device.
You will find more information in document 009078. See chapter 'Applicable
documents'.
See also
1 Applicable documents [ 11]
14.5 Replacing 'Manual call point' of the same type
NOTICE
Incorrect assignment between detector/detector zone and customer text
Inaccurate messages in the event of an alarm
You must not change the FDnet topology at the same time as adding extra
devices.
After extending or changing a 'Site' always run a test to check the
assignment between detector/detector zone and
customer text.
You will find additional information about the individual steps on the specified
pages.
1. Switch on the replace mode. Link [ 55]
2. Replace the 'Manual call point' with a 'Manual call point' of the same type.
3. Switch off the replace mode. Link [ 55]
4. Test the 'Manual call point'. Link [ 55]
5. Switch normal operation on. Link [ 90]
6. Connect the PC to the 'Station'. Link [ 27]
7. Load the configuration from the 'Station' to the PC. Link [ 32]
8. Test the function of the 'Site'. Link [ 91]
9. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [ 30]
10. Disconnect the PC from the 'Station'. Link [ 27]
You will find more information about installing and uninstalling in the
documentation for the corresponding 'Manual call point'.