Because of the fact that the FC2080 fire control panel has no integrated operating
unit, you must configure at least one operating unit within the 'Site' in such a way
that it has a ↑ visibility of the FC2080.
Commissioning
1. Create a 'SintesoWorks' and the ↑ 'Site' in Stations and pre-configure, if
required.
2. Configure the visibility of the FC2080 in SintesoWorks. You will find information
on this in the following chapter.
3. Follow the commissioning steps in chapter 'C- Commissioning networked
'Stations' [➙ 43]'.
Configuring ↑ visibility on FC2080
Figure 2: Configuring visibility on FC2080
ϖ The 'FC2080' element is present in the structure tree.
ϖ The ↑ 'Stations' that are to have a ↑ visibility of the FC2080 are present in the
structure tree.
1. Select the 'Operation' task card.
2. In the tree view, open the 'Station' that is to have a visibility of the FC2080.
3. Open the 'PMI' window and highlight the 'Standard visibility' element.
4. In the menu bar, click on 'Assign'.
The 'Assign dialog' window opens.
5. Select the desired visibility on the left in the window.
6. On the right in the window, select the 'FC2080' element.
7. Click on 'Assign'.
The visibility on the FC2080 is configured.