Detailed commissioning steps
Switching on test mode
21
89 |
188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
21.20 Switching on test mode
1. Select 'Topology' > 'Detection tree' in the main menu.
2. Select the element you want to switch to test mode: 'Area', 'Section', or 'Zone'
3. Press the 'More Options' softkey and select 'Execute commands'.
4. Select a command from the following table.
The yellow 'DETECTOR TEST' LED lights up.
The element is in test mode.
Element Command
Area 'Non-MCP zones det.test'
'MCP zones det.test'
Section 'Non-MCP zones det.test'
'MCP zones det.test'
Zone 'Detector test'