Detailed commissioning steps
21
79 |
Building Technologies
21.4 Auto-configuring 'Station'
1. Select 'Topology' > 'Hardware tree' > ↑ 'Station' in the main menu.
2. Press the 'More Options' softkey and select 'Execute commands'.
3. Select the 'Auto-configure station' command.
The 'Station' is auto-configured.
The following message is shown following successful ↑ auto-configuration:
'Command executed'
See also
1 Applicable documents [➙ 11]
21.5 Auto-configuring the detector line
NOTICE
Incorrect order for reading in a
loop, no isolation of second '
Error when reading in a loop
The FDnet detector lines are detected as ↑ stubs during the first system startup,
e.g., 'Line' 11, 'Line' 12 (2-digit line number), even if they are connected as a loop.
● Before you proceed to reading in the first 'Line', you must isolate the second
'Line'.
● To read in a loop, always select the first 'Line', in this case 'Line' 11. 'Line' 12
is then read in automatically and a loop is displayed with a 1-digit line number,
in this case as 'Line' 1.
Proceed in the same way from '
NOTICE
Overwriting an existing configuration
Parts of an existing customer-specific configuration are lost.
First save an existing customer
1. Select 'Main menu' > 'Topology' > 'Hardware tree' > ↑ 'Station' > 'Module' (line
card) > 'Line'.
2. Press the 'MoreOptions' softkey and select 'Execute commands'.
3. Select the 'Auto-configure line' command.
The FDnet detector line is auto-configured.
The following message is shown following successful ↑ auto-configuration:
'Command executed'
See also
1 Applicable documents [➙ 11]