Commissioning security module (firewall) FN2009
A1 using Internet browser
23
95 |
Building Technologies
23 Commissioning security module (firewall)
FN2009-A1
This description focuses on correctly configuring and integrating the 'Security
module (firewall) FN2009-A1' in the fire detection installation. More information
about the product can be found on the data carrier in the scope of supply and at
the following address: http://support.automation.siemens.com (Manufacturer
designation: Scalance S612)
A configuration is available via the localization manager. We recommend using
the configuration and if necessary making system-specific adaptations.
Commissioning
1. Install the 'Security Configuration Tool' software. Link [➙ 96]
2. Select the type and enter the MAC address. Link [➙ 97]
3. Enter the network settings. Link [➙ 98]
– Load configuration.
4. Create IP service definitions. Link [➙ 100]
5. Create firewall rules. Link [➙ 101]
– Load configuration.
Security module (firewall) FN2009
' is a class A equipment and may
cause radio interference in residential areas. If interference does occur, observe
the relevant information in document 008851. See chapter 'Applicable
documents'.
A1 has no IP address in the factory
setting. You must manually
assign the IP address.
NOTICE
A1 is not in factory setting and already has an IP address
It is not possible to upload a new configuration
Press the Reset button on the live FN2009