Commissioning security module (firewall) FN2009
-
A1
Configuring FN2008
-
A1 using Internet browser
23
95 |
188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
23 Commissioning security module (firewall)
FN2009-A1
This description focuses on correctly configuring and integrating the 'Security
module (firewall) FN2009-A1' in the fire detection installation. More information
about the product can be found on the data carrier in the scope of supply and at
the following address: http://support.automation.siemens.com (Manufacturer
designation: Scalance S612)
A configuration is available via the localization manager. We recommend using
the configuration and if necessary making system-specific adaptations.
Commissioning
1. Install the 'Security Configuration Tool' software. Link [ 96]
2. Select the type and enter the MAC address. Link [ 97]
3. Enter the network settings. Link [ 98]
Load configuration.
4. Create IP service definitions. Link [ 100]
5. Create firewall rules. Link [ 101]
Load configuration.
The '
Security module (firewall) FN2009
-
A1
' is a class A equipment and may
cause radio interference in residential areas. If interference does occur, observe
the relevant information in document 008851. See chapter 'Applicable
documents'.
The FN2009
-
A1 has no IP address in the factory
setting. You must manually
assign the IP address.
NOTICE
FN2009
-
A1 is not in factory setting and already has an IP address
It is not possible to upload a new configuration
Press the Reset button on the live FN2009
-
A1.