EasyManua.ls Logo

Siemens FS20 - Network Parameters

Siemens FS20
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connectivity and communication with 'Station'
Network parameters
4
26 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
5. Set the following values:
'Protocol type': 'UDP'
'Local port': 'Specific Ports', and enter the value range '50067-50070' in the
box.
'Remote port': 'All Ports'
6. Confirm with 'OK'.
The new firewall rule is now configured.
NOTICE
Security vulnerability in operating system due to open ports
Unauthorized access to your PC
Deactivate the firewall rule configured above after the firmware update.
4.2 Network parameters
Ports in FS20
Use Port number
Transport
protocol
Application
protocol
Comment
Communication
Station-to-station
communication
50501 UDP FCnet
Communication between
Engineering Tool and
station
51000 UDP FCnet
Communication between
management station and
FS20 station
47808-47823 UDP BACnet Dependent on configuration
Between BAC0 and BACF by
default
Monitoring
Station to station 50502 UDP FCnet
Remote access via cRSP
Between Engineering Tool
and station
51001-51250 UDP FCnet Dependent on configuration
Rule for ports: portHost =
51000 + hostID
Firmware update
Engineering tool 50067 UDP FW update
Panel 50068 UDP FW update
Engineering tool 50069 UDP FW update
Engineering tool 50070 UDP FW update