Updating the firmware
Updating the FW
of the peripheral devices
29
142 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
29.8.3 Floor repeater display FT2011
WARNING
Incorrect assignment between detector/detector zone and customer text
Misleading messages in the event of an alarm
Never change the wiring during the
firmware update.
The firmware must be updated individually for each floor repeater display.
Preparation
ϖ The floor repeater display is fed by a 24 V external power supply or by the
FDnet detector line.
ϖ The driver for the MCL-USB adapter FDUZ221 or FDUZ227 is installed on the
PC.
1. Select 'File' > 'Import new resource package'.
2. In the selection window, open an F-FXS2001-XX_x_x...zip file that matches the
'Site'.
3. Open the device and connect the PC via the MCL-USB adapter to the device.
Figure 9: Connect the PC to the floor repeater display
FDUZ221 /
FDUZ227
MCL-USB adapter (interface USB/MC-LINK)
X100 Connection for the MCL-USB adapter
FT2011 Floor repeater display
24 V
FT2011
X100
MC-Link
FDUZ221/FDUZ227
USB