Commissioning Ethernet switch (MM) FN2008
-
A1
Install Primary Setup Tool
22
92 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
22 Commissioning Ethernet switch (MM)
FN2008-A1
This description focuses on correctly integrating the 'Ethernet switch (MM)
FN2008-A1' in the fire detection installation. More information about the product
can be found on the data carrier in the scope of supply and at the following
address: http://support.automation.siemens.com (Manufacturer designation:
Scalance X204-2)
NOTICE
Alternate products for '
Ethernet switch (MM) FN2008
-
A1
'
No compliance with EN 54
For an EN-54-compliant fire detection installation, you must use the permitted
'
Ethernet switch (MM) FN2008
-
A1
'.
The '
Ethernet switch (MM) FN2008
-
A1
' is a class A equipment and may cause
radio interference in residential areas. If interference does occur, observe the
relevant information in document 008851. See chapter 'Applicable documents'.
Commissioning
1. Install the 'Primary Setup Tool' software. Link [ 92]
2. Assign the IP address. Link [ 93]
3. Configure the FN2008-A1 using the Internet browser. Link [ 94]
4. In SintesoWorks, create the links you want e.g., for the following monitoring
functions in a 'Technical zone'.
Redundant power
Display error contact
You will find detailed instructions on creating a
link in document
009078
. See
chapter 'Applicable documents'.
The FN2008
-
A1 has no IP address in the factory setting. You
must manually
assign the IP address.
22.1 Install Primary Setup Tool
The 'Primary Setup Tool' software is included in the scope of supply for the
FN2008-A1.
κ Start 'Primary Setup Tool' installation.
Primary Setup Tool is installed.
The DLC and PROFINET RT protocols are installed.
Primary Setup Tool recognizes one or more connected FN2008-A1 without IP
address via the DLC protocol.
The FN2008
-
A1 is displayed as X204
-
2 in Primary Setup Tool.