EasyManua.ls Logo

Siemens FS20 - Read in Devices on Detector Line; Detaching the Device

Siemens FS20
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Detailed commissioning steps
Read in devices on detector line
21
85 |
188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
21.14 Read in devices on detector line
NOTICE
Incorrect order for reading in a
loop
Error when reading in a loop.
The FDnet detector lines are detected as stubs during the first system startup,
e.g., 'Line' 11, 'Line' 12 (2-digit line number), even if they are connected as a loop.
For loop with line separator: Switch the second 'Line' / 'Line' 12 off.
To read in a loop, always select the first 'Line', in this case 'Line' 11. 'Line' 12
is then read in automatically.
A loop is displayed with a 1-digit line number, in this case as 'Line' 1 once it
has been read in.
Proceed in the same way from '
Line
'
21/22 (loop 2) to '
Line
'
41/42 (loop 4).
ϖ For loop with line separator: The second 'Line' is switched off. Link [ 82]
1. In the main menu, select 'Topology' > 'Hardware tree' > 'Station' > Line
card > Detector line.
2. Press the 'More Options' softkey and select 'Execute commands'.
3. Select the 'Read in installed devices' command.
The FDnet devices are read in.
The following message is shown following successful reading in:
'Command executed'
21.15 Detaching the device
If you want to permanently remove a device, uninstall the device and, if required,
the base and connect the wires of the detector line.
You will find more information about installing and uninstalling in the
documentation for the corresponding device.

Table of Contents

Other manuals for Siemens FS20

Related product manuals