Siemens FS20 - Line Fault Error Message; Troubleshooting Procedure; Checking the Collective Detector Line

Siemens FS20
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning control panel with collective detector lines
Troubleshooting procedure
16
60 | 188
Building
Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
16.3.1 'Line Fault' error message
If the error message 'Line fault' is displayed for collective detector lines once the
'Station' has started, the cause may be a change in line resistance.
Greater resistance, e.g. due to corrosion of the base connections or faulty end-
of-line element
Less resistance e.g. due to a defective 'Detector' or a faulty end-of-line element
See also
1 Reference measurement with EOL 4k7 and 3k3 [ 59]
1 Checking line resistance [ 61]
16.4 Troubleshooting procedure
You will find additional information about
the individual steps on the specified
pages.
1. Test the collective detector line. Link [ 60]
2. Test the line resistance. Link [ 61]
3. Test the line continuity. Link [ 61]
4. Measure the insulation values. Link [ 62]
5. Commission the collective detector line step-by-step. Link [ 63]
16.4.1 Checking the collective detector line
When testing collective detector lines on the line card (collective) FCL2002, you
must observe the following points:
Detectors must not be triggered too soon after each other.
The total time required to check a collective detector is 50 s.
Once a detector has been triggered, the internal alarm indicator flashes for
15 s and the line is automatically reset.
The length of time after which the line is ready for the next detector to be
triggered varies depending on the line type.
Type Total time required
Transzorb 45 s
EOL22Ex 40 s
EOL 4k7 50 s
EOl 3k3 50 s
Table 3: Total time required to check a collective detector