Commissioning control panel with collective detector lines
Troubleshooting procedure
16
62 | 188
Building
Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
16.4.4 Measuring insulation values
1. Switch the collective detector line off:
Switch off the 'Zone' that is assigned to the collective detector line. The
'Zone' and the physical collective detector line are then switched off at the
same time. Link [ 82]
2. Remove all 'Detectors' from bases and put base covers in their place.
3. Remove the wires from the connections on the line card.
4. Release the end unit from the connection terminal and leave the connection
open.
5. Perform the following isolation measurements with the ohmmeter at a
maximum measurement voltage of 10 V.
Each conductor to each conductor: >1 MΩ
Each conductor to earth: >1 MΩ
Each conductor to shielding: >1 MΩ
Shielding to earth: >1 MΩ
6. If these values are not reached, check the installation for the following causes:
Damp or wet installation or devices.
Troubleshooting
1. Disconnect the collective detector line in the middle by, e.g., removing the
base cover.
2. Measure each line half on its own.
3. Disconnect the faulty section, again in the middle.
4. Once the fault has been rectified, reconnect the disconnected line sections
correctly and measure the entire collective detector line.
5. Reinsert the end-of-line element and the 'Detectors'.
6. Connect the collective detector line to the control panel.