Commissioning Ethernet switch (MM) FN2008
A1 using Internet browser
22
94 | 188
22.3 Configuring FN2008-A1 using Internet browser
is available via the localization manager. We recommend using
the configuration and if necessary making system-specific adaptations.
NOTICE
Incorrect settings of the ports
Malfunction
The factory setting 'auto
negotiation' for the ports may not be
1. Open the Internet browser and enter the FN2008-A1's IP address in the
address field.
The login window opens.
2. Login:
– User name = 'admin'
– Password = 'admin'
3. Select 'System' > 'Passwords' in the tree view and set a new password for the
following fields:
– 'New User Password'
– 'New Admin Password'
4. Confirm the entered password with 'Confirmation'.
5. Click 'Set Values'.
6. Select 'X204-2' > 'Ring' in the tree view and check the 'Enable ring redundancy'
checkbox.
– Select the 'Automatic Redundancy Detection' redundancy mode.
7. Select 'X204-2' > 'Fault Mask' in the tree view and check the
'Enable Link Down Monitoring' checkbox for each connected port:
– Port 5 and 6 = Ring
– Port 1 = The connected ↑ 'Station'
– Port 2 to 4 only if more stations 'Stations' are connected
FN2008-A1 is configured.