31
166 | 188
31.2 Spare parts
● You will find details for ordering spare parts for 'Stations' in document 009690.
● You will find details for ordering Detectors and accessories in document
008164.
See chapter 'Applicable documents'.
See also
1 Applicable documents [➙ 11]
31.3 Fault messages on the Person Machine Interface
Fault messages on fire control panel FC20xx / fire terminal FT2040
Figure 14: Fault indicators on the ↑ Person Machine Interface
The table below shows the causes and measures should a fault be displayed on a
fire control panel FC20xx or fire terminal FT2040.
LED LED flashes Cause What must be done
1 FAULT The 'Site' has a fault
● Check whether another fault LED is
flashing, if not:
– Check the display
– Check whether the 'Fault' control
input is activated
5 Fault System Failure of the main CPU ● Visual check of the cable connections
● Check whether the red LED H37 on the
operating unit FCM20xx is on:
– Exchange PMI & mainboard
'Fault' of a component ● Restart ↑ 'Station'
– When the 'Fault' is still indicated:
Exchange the module
Communication fault of a
networked 'Station'
● Check the transmission line
● Check the faulty 'Station'
5
1
12
10
8