Repair
Fault m
essages on the Person Machine Interface
31
167 |
188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
LED LED flashes Cause What must be done
8
Fault / Off Remote
alarm
Remote transmission has a
'Fault'
Check remote transmission
10
Fault / Off Alarm
device
'Fault' affecting acoustic
control lines
Check the 'Line' for open circuit/short-
circuit or end-of-line element (EOL) is
missing or defective
12
Fault / Off Control
function
'Fault' affecting fire control
lines
Check the 'Line' for open line/short-circuit
Check the function of the external control
devices
Check the function, any existing
feedback switch
Fault messages on fire terminal (Touch) FT2080
Figure 15: Fault LEDs on the FT2080
The table below shows the causes and measures should a fault be displayed on a
fire terminal FT2080. Faults are displayed by LEDs and/or symbols in the system
tabs on the display. You will find more information about the layout and functions of
the symbols on the FT2080 touch screen in document A6V10380629. See
'Applicable documents'.