4.8 Loading configuration from the station to the PC
The 'Upload site' function can be used to load the configuration of a 'Site' to
SintesoWorks on the PC.
ϖ The 'Site' is opened in SintesoWorks.
ϖ The PC is connected to the 'Station'.
ϖ 'Station' and SintesoWorks have the same 'Site' ID.
ϖ 'Station' and SintesoWorks are part of the same sales channel.
1. Select 'Commissioning' > 'Upload site'.
The 'Upload site' and 'Connect' windows are opened.
2. Select the connection in the 'Connect' window and click on 'OK'.
The 'Stations' are listed in the 'Upload site' window.
3. Select the 'Stations' whose configuration you would like to load to
SintesoWorks and click on 'Start'.
The 'Action confirmation' window opens.
4. Click on 'Yes'.
The configuration is loaded to the PC.
The progress is displayed in the 'Upload site' window.
4.9 Creating a backup of the 'Site' configuration
With the 'Create backup embedded configuration' function, you can create a
backup file of the 'Site' configuration.
The following conditions must be satisfied for a complete backup:
All of the 'Stations' in the 'Site' must be networked and commissioned.
The 'Site' IDs for all 'Stations' must match the 'Site' ID for the 'Site' loaded in
SintesoWorks.
The BDVs for all 'Stations' must be compatible with the BDV for the 'Site'
loaded in SintesoWorks.
The BDVs are compatible when the major version and the minor version
are identical. The bugfix version is not relevant for the compatibility. The
versions are saved in the BDV file name. You will find more information on
the format of the BDV file name in document 009078.
The country codes of the BDVs for all 'Stations' must match the BDV for the
'Site' loaded in SintesoWorks.
You will find information about
BDV names and versions in document
009078
.
See chapter 'Applicable documents'.
If the above-mentioned conditions are not satisfied, a corresponding message is
displayed and an incomplete backup file created. In this instance, 'incomplete' is
added to the file name of the backup file.