Connectivity and communication with 'S
Loading configuration from the PC to the station
4
31 |
Building Technologies
ϖ The ↑ 'Site' is opened in SintesoWorks.
ϖ The PC is connected to the 'Station'.
ϖ Networked 'Stations' are initialized.
ϖ 'Station' and SintesoWorks have the same 'Site' ID.
ϖ 'Station' and SintesoWorks are part of the same sales channel.
1. Select 'Commissioning' > 'Download site' in SintesoWorks.
The 'Download site' and 'Connect' windows open in SintesoWorks.
2. Select the connection in the 'Connect' window and click on 'OK'.
The 'Stations' are listed in the 'Download site' window.
3. Select the 'Stations' whose configuration you would like to load from
SintesoWorks to the 'Stations' and click on 'Start'.
The 'Set access level' window may open in SintesoWorks with the 'Set the
station to access level 3' prompt. Press <MENU> on the 'Station', enter the
PIN and press <ok>.
4. Click on 'OK' in the 'Set access level' window in SintesoWorks.
The 'Action confirmation' window opens in SintesoWorks.
5. Click on 'Yes'.
The configuration is loaded to the 'Station'.
The progress is displayed in the 'Download site' window in SintesoWorks.
The 'Station' restarts.
After a few minutes, the 'Buzzer' sounds twice at the 'Station'.
6. Press <Acknowledge> on the ↑ Person Machine Interface at the 'Station' to
switch off the 'Buzzer'. Do not perform any more actions on the 'Station' until
the 'Buzzer' has sounded for the second time.
See also
1 Loading data to the 'Station' [➙ 28]