Changing and expanding the FDnet/C
Replacing stationary devices of the sa
14
50 | 188
14.1.2 Configure a new device
1. Extend the configuration in SintesoWorks, e.g., in the ↑ 'Detection tree'.
2. Allocate the read-in devices to the elements of the detection tree or the control
tree in SintesoWorks.
3. If required, configure additional 'Controls' (also for several 'Stations') using the
layout plan or finalize available 'Controls'.
14.2 Replacing stationary devices of the same type
NOTICE
Incorrect assignment between detector/detector zone and customer text
Inaccurate messages in the event of an alarm
● You must not change the FDnet topology at the same time as adding extra
devices.
● After extending or changing a ↑ 'Site' always run a test to check the
assignment between detector/detector zone and customer text.
find additional information about the individual steps on the specified
pages.
1. Switch the FDnet detector line off. Link [➙ 82]
2. Replace the FDnet device with a device of the same type. Several devices can
be replaced.
3. Rectify localization errors. Link [➙ 91]
4. Connect the PC to the ↑ 'Station'. Link [➙ 27]
5. Load the configuration from the 'Station' to the PC. Link [➙ 32]
6. Test the function of the 'Site'. Link [➙ 91]
7. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [➙ 30]
8. Disconnect the PC from the 'Station'. Link [➙ 27]
You will find information about installing and uninstalling in the documentation for
the corresponding 'FDnet' device.
You will find more information on replacing radio detectors in documents 009865
and A6V10227639. See chapter 'Applicable documents'.
See also
1 Applicable documents [➙ 11]