Updating the firmware
Update only the BDV
29
135 |
188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
10. Press <Acknowledge> on the Person Machine Interface to switch off the
'Buzzer'. Do not perform any more actions on the 'Station' until the 'Buzzer' has
sounded for the second time.
11. Click on 'Close' in the 'FW update additional CPUs' window.
See also
1 Preparation and security [ 117]
29.4 Update only the BDV
If the old and new BDVs are compatible (identical major and minor versions) and
there is no new firmware version available for the main CPU, it is also only possible
to update the BDV. You will find Information about BDV names and versions in
document 009078. See chapter 'Applicable documents'.
The procedure for updating the BDV depends on the 'Station' function. The
procedures are described in the following chapters.
See also
1 Applicable documents [ 11]
29.4.1 Standalone station and SAFEDLINK station
You will find additional information about the individual steps on the specified
pages.
ϖ Familiarize yourself with the information in 'Preparation and security [ 117]'.
1. Import the new BDV into SintesoWorks.
Select the 'File' > 'Import new BDV' menu item and open the file you want.
2. Load the configuration from the 'Station' or your archive to the PC. Link [ 32]
3. Convert the configuration and rectify conversion faults. Link [ 136]
4. Connect the PC to the 'Station'. Link [ 27]
5. Enable the 'Station'.
Press <MENU> and enter a valid PIN.
6. Load the converted configuration from the PC to the 'Station'. Link [ 30]
7. Disconnect the PC from the 'Station'. Link [ 27]