Commissioning overview
Standard gateway
5
36 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
5.3 Standard gateway
The standard gateway address of the station is pre-configured as
192.168.200.254. When using a router, an address does not need to be set at the
station. Following startup, the station automatically connects to the router. A tool is
not required to establish a remote connection.
Station Router
IP address: 192.168.200.1 192.168.200.254
Subnet mask: 255.255.255.0 255.255.255.0
Standard gateway: 192.168.200.254
5.4 Brief instructions on operating the 'Station'
Fire control panel FC20xx / Fire terminal FT2040
Buttons Description
= <MENU>
Opens the main menu
<▲> and <>
Navigation buttons for selecting the next or previous
entry in a list
<◄> and <>
Navigation buttons for changing to a higher or lower
level in the hierarchy
= <ok>
Opens or runs a selected entry or menu item
= <C>
Cancels all operating procedures and closes an open
list or an open window
<1> to <9> Buttons on the keypad to enter:
PIN
Shortcut
Address
Parameters
Customer text
You will find detailed instructions for operating the 'Stations' in document
008838. See chapter 'Applicable documents'.