Changing and expanding the FDnet/C
-
NET detector line
Replacing 'Manual call point' of the
same type
14
55 |
188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
14.5.1 Switching on the replace mode
1. Select 'Functions' > 'All functions' > 'Detector' in the main menu.
2. In the 'Zone', enter the 'Zone' address and press <ok>.
3. Enter the detector address in 'Detect.' and press <ok>.
4. Select the 'Device replace mode ON' menu item.
The following message is shown following successful switching on: 'Command
executed'.
The yellow 'ISOLATION' LED lights up.
The detector line is de-energized.
14.5.2 Switching off replace mode
1. Select 'Functions' > 'All functions' > 'Detector' in the main menu.
2. Enter the zone address in 'Zone' and press <ok>.
3. Enter the detector address in 'Detect.' and press <ok>.
4. Select the 'Device replace mode OFF' menu item.
The following message is shown following successful switching off: 'Command
executed'.
The yellow 'ISOLATION' LED goes out.
The yellow 'DETECTOR TEST' LED lights up.
The 'Manual call point' is in test mode.
14.5.3 Testing 'Manual call point'
1. Check whether the 'Manual call point' is in test mode using the LED.
2. Activate the 'Manual call point' using the corresponding tools.
You will find information about this in the 'Manual call point' documentation.