B1
-
Commissioning standalone 'Station' with PC, without pre
-
configuration
7
41 |
188
Building Technologies
009052_s_en_
--
Fire
Safety
2016
-
-
02
7 B1 - Commissioning standalone 'Station' with
PC, without pre-configuration
First auto-configure the 'Station' in this commissioning variant. Then adapt the
auto-configuration manually in SintesoWorks.
The procedure in this chapter applies exclusively to
standalone '
Stations
' and is
only valid for FDnet detector lines.
Prerequisites
The detector lines and FDnet devices are installed.
The acceptance test has been carried out for the detector lines.
The 'Station' is installed, but the batteries are not connected yet.
The cables for the detector lines and the mains supply have been inserted in
the 'Station', but not yet connected.
SintesoWorks is installed on the PC.
The current firmware and BDV are available on the PC.
You will find additional information about the individual steps on the specified
pages.
Commissioning
1. Prepare the 'Station' for commissioning. Link [ 76]
2. Perform auto-configuration:
Auto-configure 'Station'. Link [ 79]
OR
Auto-configure detector lines individually. Link [ 79]
3. Connect the PC to the 'Station'. Link [ 27]
4. Load the automatically created configuration to the PC. Link [ 80]
5. Adapt the configuration in SintesoWorks. Link [ 80]
6. Load the configuration from the PC to the 'Station'. Link [ 30]
7. Test the function of the 'Site'. Link [ 91]
8. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [ 30]
9. Disconnect the PC from the 'Station'. Link [ 27]
10. Perform the completion tasks. Link [ 91]