29.7 Creating diagnosis report
To update the firmware versions for the creation of the diagnosis report, the
configuration data must be loaded in SintesoWorks.
ϖ The configuration data for the ↑ 'Station' is loaded to SintesoWorks.
1. Select 'Commissioning' > 'Diagnostics report' from the menu bar.
The 'Reports' window opens.
2. Select the 'Diagnostics report' element in the 'Report type' field.
3. Select the page format, page orientation, file name and memory location of the
report in the 'Output settings' section.
4. Click on 'Create report'.
The report is created and displayed.
You will find more information about creating reports and the diagnosis report in
document 009078. See chapter 'Applicable documents'.
See also
1 Applicable documents [➙ 11]
29.8 Updating the FW of the peripheral devices
You need the following tools to update the firmware of the peripheral devices:
● SintesoWorks
● MCL-USB adapter FDUZ221 or FDUZ227
If the hardware product version is not compatible with the current firmware,
corresponding error message is displayed during the update process.
In this instance, the hardware must be replaced in accordance with the
information in the 'Release Notes'.