Repair
Restoring factory setting
on the station
31
172 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
CPU card
1. Briefly press the 'S8' button on the CPU card until a 'R' is displayed on the LED
matrix display.
2. As soon as the 'R' is displayed, press and hold the 'S8' button for approx. 2 s to
confirm the selection.
A checkmark on the LED matrix display confirms the selection.
The CPU card is restarted.
You will find information on the
CPU card FCC2004, the LED matrix display,
and operating the 'S8' button in document 008837. See chapter 'Applicable
documents'.
See also
1 Applicable documents [ 11]
31.10 Restoring factory setting on the station
There are the following ways in which to restore the factory setting on the
'Station':
Via the menu on the display
PMI & mainboard FCM2004 and FCM2027: With the 'S32' button
CPU card: With the 'S8' button
Via the menu on the display
1. Press <MENU>.
You are prompted to enter a PIN.
2. Enter a valid PIN and confirm with <ok>.
The 'User successfully logged in' message is displayed.
The main menu is displayed.
3. Select the 'Topology' > 'Hardware tree' > 'Station' menu items.
4. Press the 'MoreOptions' softkey and select 'Execute commands'.
5. NOTICE! Configuration will be deleted! Save the configuration data for the
'Station' before restoring the factory setting.
6. WARNING! It is impossible to acquire and process alarms or faults without a
site configuration! Select the 'Factory reset' command.
The 'Station' restarts.
7. Enter the date and time. To do this, select the 'Settings/administration' >
'System commands' > 'Set system time' menu items.