Updating the FW of the peripheral devices
29
140 | 188
29.8.2 Floor repeater terminal FT2010
WARNING
Incorrect assignment between detector/detector zone and customer text
Misleading messages in the event of an alarm
Never change the wiring during
The firmware must be updated individually for each ↑ floor repeater terminal.
Preparation
ϖ The ↑ floor repeater terminal is fed by a 24 V external power supply or by the
FDnet detector line.
ϖ The driver for the MCL-USB adapter FDUZ221 or FDUZ227 is installed on the
PC.
1. Select 'File' > 'Import new resource package'.
2. In the selection window, open an F-FXS2001-XX_x_x_...zip file matching the
↑ 'Site'.
3. Open the device and connect the PC via the MCL-USB adapter to the device.
Figure 8: Connect the PC to the floor repeater terminal
FDUZ221 /
FDUZ227
MCL-USB adapter (interface USB/MC-LINK)
X100 Connection for the MCL-USB adapter
FT2010 Floor repeater terminal
24 V
X100
MC-Link
FDUZ221/FDUZ227