Updating the firmware
Updating the FW of the peripheral devices
29
140 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
29.8.2 Floor repeater terminal FT2010
WARNING
Incorrect assignment between detector/detector zone and customer text
Misleading messages in the event of an alarm
Never change the wiring during
the firmware update.
The firmware must be updated individually for each floor repeater terminal.
Preparation
ϖ The floor repeater terminal is fed by a 24 V external power supply or by the
FDnet detector line.
ϖ The driver for the MCL-USB adapter FDUZ221 or FDUZ227 is installed on the
PC.
1. Select 'File' > 'Import new resource package'.
2. In the selection window, open an F-FXS2001-XX_x_x_...zip file matching the
'Site'.
3. Open the device and connect the PC via the MCL-USB adapter to the device.
Figure 8: Connect the PC to the floor repeater terminal
FDUZ221 /
FDUZ227
MCL-USB adapter (interface USB/MC-LINK)
X100 Connection for the MCL-USB adapter
FT2010 Floor repeater terminal
24 V
FT2010
X100
MC-Link
FDUZ221/FDUZ227
USB