Updating the firmware
Updating the FW of the peripheral devices
29
152 | 188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
Updating the firmware
Check the COM port setting under '
Options
' > '
Preferences
' > '
Periphery update
'
before performing the firmware update.
1. Select 'Update' > 'Periphery update wizard'.
2. In the 'Password check' window, enter the password '1234' and click on the
'Next' button.
3. In the 'Devices:' field, select the 'FDUL221 FDnet line test device'.
The connection with the line tester is established.
4. Press and hold down the '', '', and '' buttons on the line tester and click on
the 'Next' button in the Engineering Tool at the same time.
5. Only release the '' button.
The device is set to update mode.
6. Release the '' and '' buttons.
7. Follow the instructions in the dialog in the Engineering Tool and perform the
update.
The line tester restarts.
8. Remove the MCL-USB adapter.
The firmware is updated.