Name Type Values (Range) Unit Description
OUT10 GROUP
SIGNAL
- - Output 10 status
OUT11 GROUP
SIGNAL
- - Output 11 status
OUT12 GROUP
SIGNAL
- - Output 12 status
OUT13 GROUP
SIGNAL
- - Output 13 status
OUT14 GROUP
SIGNAL
- - Output 14 status
OUT15 GROUP
SIGNAL
- - Output 15 status
OUT16 GROUP
SIGNAL
- - Output 16 status
OUTOR GROUP
SIGNAL
- - Output status logic OR
gate for input 1 to 16
18.3.4.6 Operation principle
Upon receiving a signal at its input, Generic communication function for Single Point
indication (SPGAPC) function sends the signal over IEC 61850-8-1 to the equipment
or system that requests this signal. Additional configuration is needed with PCM600
or IET600 to get the IEC 61850-8-1 communication established For more information
refer to the Engineering manual.
18.3.5 Generic communication function for Measured Value
MVGAPC
18.3.5.1 Functionality
Generic communication function for Measured Value MVGAPC function is used to
send the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an
analog value and to permit measurement supervision on that value.
18.3.5.2 Function block
MVGAPC
BLOCK
^IN
^VALUE
RANGE
IEC14000022-1-en.vsd
IEC14000022 V1 EN
Figure 463: MVGAPC function block
1MRK502052-UEN B Section 18
Station communication
997
Technical manual