EasyManua.ls Logo

ABB REG670 - Functionality; Technical Data

ABB REG670
1298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.1.7 Technical data
Table 74: ZMHPDIS technical data
Function
Range or value Accuracy
Number of zones, Ph-E Max 4 with selectable direction -
Minimum operate current (10–30)% of IBase -
Positive sequence impedance,
Ph-E loop
(0.005–3000.000) W/phase
± 2.0% static accuracy
Conditions:
Voltage range: (0.1-1.1) x U
r
Current range: (0.5-30) x I
r
Angle: 85 degrees
Positive sequence impedance
angle, Ph-E loop
(10–90) degrees
Reverse reach, Ph-E loop
(Magnitude)
(0.005–3000.000) Ω/phase
Magnitude of earth return
compensation factor KN
(0.00–3.00)
Angle for earth compensation
factor KN
(-180–180) degrees
Dynamic overreach <5% at 85 degrees measured
with CVT’s and 0.5<SIR<30
-
Definite time delay Ph-Ph and Ph-
E operation
(0.000-60.000) s ± 0.2% or ± 60 ms whichever is
greater
Operate time 22 ms typically IEC 60255-121
Reset ratio 105% typically -
Reset time at 0.5 to 1.5 x Zreach Min = 30 ms
Max = 45 ms
-
7.2 Directional impedance element for mho
characteristic ZDMRDIR
7.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional impedance element for mho
characteristic
ZDMRDIR
S00346 V1 EN
21D
7.2.2 Functionality
The phase-to-earth impedance elements can be supervised by a phase unselective
directional function based on symmetrical components (option).
1MRK502052-UEN B Section 7
Impedance protection
197
Technical manual

Table of Contents

Other manuals for ABB REG670

Related product manuals