4.1.3.2 Setting parameters for binary input/output module
Table 21: IOMIN Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - On Binary input/output module in operation
(On) or not (Off)
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit
Section 4 1MRK502052-UEN B
Binary input and output modules
76
Technical manual