15.12.5 Setting parameters
The function does not have any parameters available in local HMI or Protection and
Control IED Manager (PCM600)
15.12.6 Operation principle
With integer 15 on the input INP the OUT1 = OUT2 = OUT3= OUT4 =1 and the
remaining OUTx = 0 for (5≤x≤16).
OUTx represents a value when activated. The value of each of the OUTx is in
accordance with the table IB16_1. When not activated the OUTx has the value 0.
In the above example when integer 15 is on the input INP the OUT1 has a value =1,
OUT2 has a value =2, OUT3 has a value =4 and OUT4 has a value =8. The sum of
these OUTx is equal to 1 + 2 + 4 + 8 = 15.
This follows the general formulae: The sum of the values of all OUTx = 2
x-1
where
1≤x≤16 will be equal to the integer value on the input INP.
The Integer to Boolean 16 conversion function (IB16) will transfer an integer with a
value between 0 to 65535 connected to the input INP to a combination of activated
outputs OUTx where 1≤x≤16. The sum of the values of all OUTx will then be equal
to the integer on input INP. The values of the different OUTx are according to the table
below. When an OUTx is not activated, its value is 0.
When all OUTx where 1≤x≤16 are activated that is = Boolean 1 it corresponds to that
integer 65535 is connected to input INP. The IB16 function is designed for receiving
the integer input locally. If the BLOCK input is activated, it will freeze the logical
outputs at the last value.
Values of each of the different OUTx from function block IB16 for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block IB16.
Name of OUTx
Type Description Value when
activated
Value when
deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
OUT10 BOOLEAN Output 10 512 0
Table continues on next page
Section 15 1MRK502052-UEN B
Logic
844
Technical manual