18.9.5 Settings
Table 796: GOOSEDPRCV Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
18.9.6 Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of
a cross to receive the double point values.
The implementation for IEC 61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the
DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
18.10 GOOSE function block to receive an integer value
GOOSEINTRCV
18.10.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive an
integer value
GOOSEINTRCV - -
18.10.2 Functionality
GOOSEINTRCV is used to receive an integer value using IEC 61850 protocol via
GOOSE.
Section 18 1MRK502052-UEN B
Station communication
1068
Technical manual