ABB REG670 - Technical Data

ABB REG670
1298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UDTripL1>
U1<L1
AND
O
R
UDAlarmL1>
UDTripL2>
UDAlarmL2>
UDTripL3>
UDAlarmL3>
AND
AND
AND
AND
AND
t
tReset
t
tAlarm
O
R
t
tTrip
TRIP
START
ALARM
U1<L2
U1<L3
U2<L1
U2<L2
U2<L3
AND
t
tAlarm
t
t1
OR
AND
AND
AND
BLOCK
AND
AND
U1LOW
U2LOW
en06000382-2.vsd
BlkDiffAtULow
AND
AND
IEC06000382 V3 EN
Figure 255: Principle logic for Voltage differential function VDCPTOV
9.5.8 Technical data
Table 297: VDCPTOV technical data
Function
Range or value Accuracy
Voltage difference for alarm and
trip
(2.0–100.0) % of
UBase
±0.5% of U
r
Under voltage level (1.0–100.0) % of
UBase
±0.5% of U
r
Independent time delay for
voltage differential alarm at 0.8 to
1.2 x UDAlarm
(0.000–60.000)s
±0.2% or ±40 ms whichever is
greater
Independent time delay for
voltage differential trip at 0.8 to
1.2 x UDTrip
(0.000–60.000)s
±0.2% or ±40 ms whichever is
greater
Independent time delay for
voltage differential reset at 1.2 to
0.8 x UDTrip
(0.000–60.000)s
±0.2% or ±40 ms whichever is
greater
1MRK502052-UEN B Section 9
Voltage protection
531
Technical manual