Figure 73: Simplified characteristic for offset mho in reverse direction for L1-to-
earth fault
7.1.6.5 Simplified logic diagrams
Distance protection zones
The design of the distance protection zones are presented for all measuring loops:
phase-to-earth as well as phase-to-phase.
Phase-to-earth related signals are designated by L1N, L2N and L3N. The phase-to-
phase signals are designated by L1L2, L2L3, and L3L1.
Fulfillment of two different measuring conditions is necessary to obtain the one
logical signal for each separate measuring loop:
Zone measuring condition, which follows the operating equations described
above.
Group functional input signal (STCND), as presented in figure
74.
The ZMHPDIS function block is used in the IED for each zone.
The STCND input signal represents a connection of six different integer values from
Phase selection with load encroachment function FMPSPDIS within the IED, which
1MRK502052-UEN B Section 7
Impedance protection
193
Technical manual