8.6.8 Technical data
Table 193: SDEPSDE technical data
Function
Range or value Accuracy
Operate level for 3I
0
·cosj
directional residual
overcurrent
(0.25-200.00)% of
lBase
± 1.0% of I
r
at I £ I
r
± 1.0% of I at I > I
r
Operate level for ·3I
0
·3U
0
cosj
directional residual power
(0.25-200.00)% of
SBase
± 1.0% of S
r
at S £ S
r
± 1.0% of S at S > S
r
Operate level for 3I
0
and j
residual overcurrent
(0.25-200.00)% of
lBase
± 1.0% of I
r
at £ I
r
± 1.0% of I at I > I
r
Table continues on next page