5.3.4 Settings
Table 28: LEDGEN Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off/On
tRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance length
tMax 0.1 - 100.0 s 0.1 1.0 Maximum time for the definition of a
disturbance
Table 29: GRP1_LED1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
SequenceType Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
-
- Follow-S Sequence type for LED 1, local HMI alarm
group 1
LabelOff 0 - 18 - 1 G1L01_OFF Label string shown when LED 1, alarm
group 1 is off
LabelRed 0 - 18 - 1 G1L01_RED Label string shown when LED 1, alarm
group 1 is red
LabelYellow 0 - 18 - 1 G1L01_YELLOW Label string shown when LED 1, alarm
group 1 is yellow
LabelGreen 0 - 18 - 1 G1L01_GREEN Label string shown when LED 1, alarm
group 1 is green
5.3.5 Monitored data
Table 30: GRP1_LED1 Monitored data
Name
Type Values (Range) Unit Description
LEDStatus INTEGER 1=Red flash
2=Red steady
3=Yellow flash
4=Yellow steady
5=Green flash
6=Green steady
0=Off
-
Status of LED 1, local
HMI alarm group 1
5.4 LCD part for HMI function keys control module
5.4.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
LCD part for HMI Function Keys Control
module
FNKEYMD1 -
FNKEYMD5
- -
Section 5 1MRK502052-UEN B
Local Human-Machine-Interface LHMI
80
Technical manual