Table 497: ALMCALH Output signals
Name Type Description
ALARM BOOLEAN OR function betweeen inputs 1 to 16
15.3.5 Settings
Table 498: ALMCALH Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
15.3.6 Operation principle
The logic for group alarm ALMCALH block is provided with 16 input signals and one
ALARM output signal. The function block incorporates internal logic OR gate in
order to provide grouping of connected input signals to the output ALARM signal
from the function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the
ALARM output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a
steady signal.
ALARM
Input 1
I
n
p
u
t
1
6
³1
200 ms
t
IEC13000191-1-en.vsd
IEC13000191 V1 EN
Figure 375: Group alarm logic
15.3.7 Technical data
Table 499: Number of ALMCALH instances
Function
Quantity with cycle time
3 ms 8 ms 100 ms
ALMCALH - - 5
Section 15 1MRK502052-UEN B
Logic
804
Technical manual