Function Range or value Accuracy
Maximum number of recordings 100, first in - first out -
Time tagging resolution 1 ms See table 844
Maximum number of analog inputs 30 + 10 (external + internally
derived)
-
Maximum number of binary inputs 96 -
Maximum number of phasors in the
Trip Value recorder per recording
30 -
Maximum number of indications in a
disturbance report
96 -
Maximum number of events in the
Event recording per recording
150 -
Maximum number of events in the
Event list
1000, first in - first out -
Maximum total recording time (3.4 s
recording time and maximum number
of channels, typical value)
340 seconds (100 recordings) at
50 Hz, 280 seconds (80
recordings) at 60 Hz
-
Sampling rate 1 kHz at 50 Hz
1.2 kHz at 60 Hz
-
Recording bandwidth (5-300) Hz -
16.7 Logical signal status report BINSTATREP
16.7.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logical signal status report BINSTATREP - -
16.7.2 Functionality
The Logical signal status report (BINSTATREP) function makes it possible for a SPA
master to poll signals from various other functions.