EasyManua.ls Logo

ABB REG670 - Technical Data

ABB REG670
1298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Slope = 0.8
Slope = 1
Operation
area
I
MinOp
99000068.vsd
phase ref
|
å
I
| - | I |
phase ref
|
å
I
| + | I
|
IEC99000068 V1 EN
Figure 287: Operate characteristics
Due to the formulas for the axis compared, |SIphase | - |I ref | and |S I
phase | + | I ref | respectively, the slope can not be above 2.
13.1.7 Technical data
Table 348: CCSSPVCtechnical data
Function
Range or value Accuracy
Operate current (10-200)% of IBase ±10.0% of I
r
at I ≤ I
r
±10.0% of I at I > I
r
Reset ratio, Operate current >90%
Block current (20-500)% of IBase ±5.0% of I
r
at I ≤ I
r
±5.0% of I at I > I
r
Reset ratio, Block current >90% at (50-500)% of IBase
13.2 Fuse failure supervision FUFSPVC
13.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fuse failure supervision FUFSPVC - -
Section 13 1MRK502052-UEN B
Secondary system supervision
606