15.1.5 Settings
Table 489: SMPPTRC Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
Program 3 phase
1ph/3ph
1ph/2ph/3ph
-
- 1ph/3ph Three ph; single or three ph; single, two or
three ph trip
tTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output signal
tWaitForPHS 0.020 - 0.500 s 0.001 0.050 Secures 3-pole trip when phase selection
failed
Table 490: SMPPTRC Group settings (advanced)
Name Values (Range) Unit Step Default Description
TripLockout Off
On
- - Off On: activate output (CLLKOUT) and trip
latch, Off: only outp
AutoLock Off
On
- - Off On: lockout from input (SETLKOUT) and
trip, Off: only inp
15.1.6 Operation principle
The duration of a trip output signal from tripping logic common 3-phase output
SMPPTRC is settable (tTripMin). The pulse length should be long enough to secure
the breaker opening.
For three-phase tripping logic common 3-phase output, SMPPTRC has a single input
(TRIN) through which all trip output signals from the protection functions within the
IED, or from external protection functions via one or more of the IEDs binary inputs,
are routed. It has a single trip output (TRIP) for connection to one or more of the IEDs
binary outputs, as well as to other functions within the IED requiring this signal.
AND
BLOCK
TRIN
Operation Mode = On
OR
t
tTripMin
TRIP
en05000789.vsd
Program = 3Ph
IEC05000789 V1 EN
Figure 367: Simplified logic diagram for three phase trip
SMPPTRC function for single-phase and two-phase tripping has additional phase
segregated inputs for this, as well as inputs for faulted phase selection. The latter
1MRK502052-UEN B Section 15
Logic
793
Technical manual